7.6 Outside temperature (OUTS)
7.6.1 Activation and functionality
You can activate the function by setting identifier OUTS (outside temperature) at
the respective input.
Activating the function
OUTS (outside temperature) is a special identifier, because it creates a large
number of internal connections.
The other properties, such as measuring range, troubleshooting, etc., are
described in chapter 0 "Analog inputs".
Additional functionality
7.6.2 Settings
Path: … > COMMIS > CONF > X1…X5
Configuration
Display Name Range / comments
LABEL Input identifier OUTS
Path: … > PARA > X1
Setting values
… > PARA > X5
Display Name Range Factory setting
TYPE Type NI, 2XNI, T1, PT, 0-10 NI
MIN VAL Value low 50…+500 -50
MAX VAL Value high 50…+500 250
CORR Correction 3.0…+3.0 0 K
Path: INFO
Display values
Display Name Comments
OUTS Outside temperature
Path: … > COMMIS > TEST
Wiring test
Display Name Positions
OUTS Outside temperature Indication of outside temperature (at
terminal Xx and as special data point
OUTS), non-adjustable
Display Name Effect
Xx --- / ooo Sensor error X… Non-urgent message; plant not stopped
Fault status messages
51 / 174
Siemens Universal Controllers RLU2… CE1P3101en
Building Technologies Inputs 29.08.2008