8.4.1 Enabling and motor block type
Enable the motor block by assigning the corresponding outputs and determining
the type for motor B.
Valid configurations:
Motor Configuration point Setting
1-speed motor Motor A
Motor B
Motor B type
Qx
---
(not relevant)
2-speed motor Motor A
Motor B
Motor B type
Qx
Qx
2-speed
Twin motor Motor A
Motor B
Motor B type
Qx
Qx
Twin motor
A free relay can be assigned to the output. For transparency, we recommend to
arrange the relays side by side.
Main menu > Commissioning > Extra configuration > Aggregates > Motor > Motor 1...6 >
Configuration
Operating lin
e Range Factor
y setting
Motor A ---, N.Q1, N.Q2, ... (free outputs only)
Motor B ---, N.Q1, N.Q2, ... (free outputs only)
Motor B type 2-speed, Twin motor 2-speed
8.4.2 1-speed motor
Use the single-speed motor to control a pump, a single-speed fan or any other
aggregate.
Purpose
Pump control via 1-speed motor.
Example
DO
N.Y1
N.Q1
A
Modul. output
Run-up and switch-off of the 1-speed motor. Switch-on delay, switch-off delay, min.
switch-on time and min. switch-off time are considered.
Control sequence
107 / 216
Siemens Switching and monitoring device RMS705B CE1P3124en
Building Technologies Aggregates 01.04.2010