9.2 Enthalpy calculator
The function block calculates the following based on inputs temperature and
relative humidity:
Purpose
Functio
n range A (inputs Temp A and RelHu A):
Functio
n rang
e A
Enthalpy
A
Abso
lute humidity A
Dew point temperature
Wet bulb temperature
Function range B (inputs Temp B and Rel Hu B):
Functio
n rang
e B
Enthalpy B
Abso
lute humidity B
Enthalpy difference (Enthalpy A Minus Enthalpy B)
The results of the calculations are provided as DC 0...10 V signals or as internal,
analog signal.
Range Inputs Outputs
A Temp A Temperature input A Enth A Enthalpy A
RelHu A Relative humidity input A Abso Hu A Absolute humidity A
Dew Pnt Dew point temperature
Wet Blb Wet bulb temperature
B Temp B Temperature input B Enth B Enthalpy B
RelHu B Relative humidity input B Abso Hu B Absolute humidity B
Enth Diff Enthalpy difference A-B
Definition of short nam
es