11.6 Start the universal controller
Configure a start condition for the universal controller.
The controller is stopped and started via a digital signal.
Note
s "Current setpoint" is displayed with "---" when a universal controller is stopped.
The controller always runs without configured start condition.
Main menu > Commissioning > Extra configuration > Controller 1...3 >
Operating line Adjustable values / Comment
Start condition ---, N.X1, N.X2, ...
(digital values only).
Starts the controller, all outputs to 0%.
11.7 Assign texts
Adapt the texts for the universal controller via operation.
Main menu > Commissioning > Settings > … or
Main menu > Settings > Controller 1...3 >
Setting values
Operating line Range Factory setting
Controller x Max. 20 characters Controller x
See Section 16.4 "Editable texts RMS705B" for an overview of all editable texts
and on how to
reset them.
176 / 216
Siemens Switching and monitoring device RMS705B CE1P3124en
Building Technologies Universal controller 01.04.2010