8.2.9 Priorities
For comparator operations, the following priorities apply:
1. On/Off during wiring test.
2. Off by "Off time minimum".
3. On by "On time minimum".
4. Off by "Switch-on delay".
5. On by "Switch-off delay".
6. Comparison of inputs Switching value A and B.
8.2.10 Troubleshooting
The output for the comparator is set to "Off" when the input values are compared to
various units or when there is a sensor error on the input.
77 / 216
Siemens Switching and monitoring device RMS705B CE1P3124en
Building Technologies Aggregates 01.04.2010