6.8 7. serial ports
The master board K3X020 (K3X030) provides 2 (1) identical serial RS232 ports. The application on these
ports is selectable.
LON-bus
or
BMS
or
VISU
or
SWE
or
Printer
Remote indicating/control equipment
3rd party
housing
BMS = Building Management System
beam
Temporary connection
Demo/Training
UP/DOWNload user data
logging printer
K3I080
RS232/LON
converter
RS232-1/-2
Note:
Each application can only
be provided once either on
RS232-1 or RS232-2
K3X020K3X030
Serial ports
RS232-1 RS232-2
Printer • for spontaneous logging
• can be disabled/enabled via operating menu
• for printer with serial RS232 interface with IBM or EPSON mode
• supervision possible RTS/CTS
• individual parameter setting
X X
LON • to drive remote indicating/control equipment via LON-bus
• only possible via RS232/LON converter card K3I080
• supervised
X X
BMS
• to connect to 3rd party system see also page 116
• two way or one way communication
• supervision possible
X X
VISU
(VISUALIZER)
• allows remote operating via PC see also page 115
• duplication of the FC330A operating interface
• temporary application
• enabling/disabling VISUALIZER-operating via operating menu
• on for demo or training
X X
SWE • to up/download parameters from/to configuration tool SWE...
• temporary application
• enabling/disabling data transfer mode via operating menu
X X
The serial ports are electrically not separated. If the system reports ’earth leak’ after the external device is
connected, the following action can be taken:
S remove the ’earth leak’ at the connected device or
S use a special separation module (RS232 to RS232) only for temporary application (SWE/VISU)
S remove temporarily
jumper ’ST2’ on the master bord
S connecting information see page 37/40