Fire Safety & Security Products
Building Technologies
1583_o_en_−−_2
33
08.2005
2.16 Connecting of conventional SynoLINE300 devices (current limited)
Note:for technical details see page 110
to run SynoLINE300 set jumper on the line extension card K3M010/020 accordingly see page 42, 43
−> list order and type of all devices (field device list)
+−
+−+−
AI322
micro terminals
AI320
Response
indicator
AI322
max. 2 response indicators
line
+
−
Smoke/heat detectors
−
+
Resistor 470Ω / 1,5W or Z-Diode 5,6V / 1,5W
alarm
contact
EOL20
+
−
Manual call points
line
+
−
−+−++−
Base SO320
OP320C
MT320C
−
+
MT320CMT320C
−+−++− −+−++−
Base SO320
Base SO320
HI32xC
OH320C
EOL20
AI322
AI320
Response
indicator
AI320
EOL20
MT320C
Resistor 1.2kΩ
−
+
Resistor 1.2kΩ
Resistor 1.2kΩ
Signal contact
S terminate each detector line with EOL20
S do not mix automatic detectors with
manual call points
S max. 32 smoke/heat detectors per line