Fire Safety & Security Products
Building Technologies
1583_o_en_−−_2
40
08.2005
Pluggable terminal block K8
Pluggable terminal block K7
Pluggable terminal block K6
Z3B171
14
12
11
A2
A1
10A / 250VAC
3
2
1
4
Programmable control input (manned)
1
2
3
4
5
6
7
8
1
2
3
4
+
+
+
5
6
F1
1A/F
F2
0,5A/F
Supply output
24V
DC
Terminals K9
Battery
Charging / monitoring
F3
2
1
+
3,15A/T
2 x 12V/12Ah
F4
emergency power battery
AX1212 or equivalent
to terminal block K1-1
Connector K12
RS232−2
air-conditio-
ning control
1st floor
Example
INPUT 0V
OUTPUT
Programmable control input (evac.)
Programmable control input (ackn.)
Programmable control input (reset)
Programmable control output 1
Programmable control output 2
Programmable control output 3
Programmable control output 4
+24V
0V
Programmable control output 5
Programmable control output 6
Programmable control output 7
Programmable control output 8
total current available for all
control outputs and 24V-power
output is 1,5A
24V / 2A/1A
BATTERY
max. 48mA
900
External voltage
side (contacts)
Control unit voltage
side (coil)
for internal and
external use
programming see page 91
from internal use only
500
default
Connector K11
RS232−1
K6
K7
K8
AC
K9
K50
K12
K11
Terminals K50
Supply input
24,5...28V
DC
F11
2
1
+
3,15A/T
F12
EXT. 24V
Remark:
depending upon battery type inserted
jumper ST8/9 or ST10
details see page 21 and 106
FC330A-x (K3X020)
* Caution !
no electrical isolation
Printer *
PC *
K3I080
K3I090
other equipment
*
Details see page 114
max. 15m between FC330A-x and printer /PC
connector
cable
connector cable
field wire
Detail see docu e1923
S active as long as is applied
S programming see page 100
1
5
6
9
TXD
RXD
GND
RTS
CTS
DCD
DTR
DSR
RI
1
5
6
9
TXD
RXD
GND
RTS
CTS
DCD
DTR
DSR
RI
RI
CTS
RTS
DSR
GND
DTR
TXD
RXD
DCD
Adapter K3K040
K1
K2
Terminals
Remark:
Input for 24V from external source instead of internal battery (K9)
Insert jumper ’ST11’ details see page 53
Mains connection see page 41

Table of Contents