2.26 Connecting LED driver card K3L100
LED outputs 17 – 32
5V / max. 15mA
short circuit proof
EMC protected
LED outputs 1 – 16
5V / max. 15mA
short circuit proof
EMC protected
to connector C
Pluggable terminal block K3
5
6
7
4
Pluggable terminal block K1
+
K3L100
LED 1
LED 1-16
6 Pan-head screws
6 washers
6 spacer bolts L=32
2 cable holders
mounting see page 25...27
LED 17-32
to B3R080
if required
in-/outputs
activates all outputs as long as input is activated
+
2
1
3
4
6
5
7
8
+
+
9
12
11
13
14
16
15
Pluggable terminal block K2
3
+
2
1
+
Output LED ’ON’ 5V/max. 15mA
Input buzzer OFF
Input lamp test
10
+
+
18
17
19
20
22
21
23
24
+
+
25
28
27
29
30
32
31
26
OUTPUT
K3L100 can be used
simultaneously with
B3R080 or by it self
INPUT / OUTPUT
LED 16
LED 17
LED 32
external LED panel
turns off output buzzer
active if 5V power inside K3L100 is ON
active as long as LED 1.....32 is active or until
input ’buzzer OFF’ is activated
max. line length 0,8mm O = ......400m
0,6mm O = ......200m
LED 1...32
S to be allocated to one or several detector
ZONE(S)
S common allocation with B3R080
(see setting user applications)
S only activated on alarm
S no serial resistor for external LEDs needed
S onboard 5V converter
Output buzzer 5V/max. 15mA