Fire Safety & Security Products
Building Technologies
1583_o_en_−−_1
2
08.2005
1.1 Features
Features FC330A-ECO... FC330A-x
Application range small installations small and medium installations
Suitable for installer market x x
Pre−assembled at factory x x
Detector loops (SynoLOOP) 1 2 + 2
Addressable Synova® detectors and input modules
...128 ...512 5)
Addressable output modules ...64 ...64
Conventional detector lines − 4 / 12 (optional)
Programmable outputs on LON−bus ...256 ...256
Programmable inputs on LON−bus ...16 ...16
Programmable outputs internal 8 (+ 12) 8 (+ 12 + 8 optional)
Programmable inputs internal 4 4
Inputs for 4 spare LEDs x x
Monitored control lines for sounders 2 (+ 2) 2 (+ 2 + 2 optional)
Monitored control lines for remote transmission − 2
Dry contacts 2 2 (+ 2 optional)
Serial ports 1 x RS232 / all applications 3) 2 x RS232 / all applications 3)
Remote indicator / control panels on LON−bus ..3 (..16) 1) ..16 4)
Remote output devices on LON−bus ..3 (..16) 1) ..16 4)
Logical zones for detectors/input modules ...128 ...512
Logical zones for control outputs ...128 ...128
Programmable alarm organization x x
Programmable multi−logic for detectors x x
System clock
− date pre-programmed until 2079
− each country with individually pre programmed holidays
− autom. summer/winter time switching for Western Europe
− clock accuracy +/− 15 min./year
x
x
x (function to enable)
x
x
x
x (function to enable)
x
Alarm counter x (1000) x (1000)
Event memory storing up to 200 events x x
Automatic reading of detector and LON−bus network x x
Automatic zone allocation on startup x x
Optional parallel indicator panel − x 2)
Optional module LED−outputs for zone ALARM − x
Optional interface card for pager system x x
Optional power supply − x
Power supply ...50VA / ..72h ..100VA (+ ..120VA opt.) / ..72h
Supply outputs 24V 1 x 0,5A 1 x 0,5A / 1 x 1A (1 x 3.15A opt.)
Supply mode
− external 24V
− mains + external 24V
− mains without battery
− mains + battery
−
−
x
x
x
x
x
x
Available cabinet sizes 1 2
Adapter for mounting into 19” cabinet x −
Cabinet door lock mechanism 2 Allen screws DOM key lock / Nordic key lock
Space for fire control relays ...4 relays ...8 relays (+ ...8 relays optional)
On site user programming configuration tool / direct configuration tool / direct
1) only possible with external power supply
2) only with FC330A-2/-2-CH/-5
3) Applications: ’LON-bus’ or ’printer’ or ’BMS’ (open interface to 3rd party)
4) for >8 resp. 10 use add-on power supply Z3I1000
5) limitation of 512 detectors and/or manual call points according to BS-EN54-2