64
08.2005
Level SERVICE FUNCTIONS
> enter password?
hm: back to menu Stop: end operating
direct setting user parameters
Access level
0011 8642
direct definition user texts
(locked with switch ’S2’)
(not locked)
to erase ’non alarm’ events
Access level
0033
connect addressable loop
disconnect addressable loop
for TEST LEDs
start automatic configuration of addr. lines
for COMMON disabling
enable / disable ’visualizer’
to start automatic configuration of LON-Bus
see page 64
Service engineer
Access level
0033
0033
0033
to activate horn briefly with each det. TEST
alarm
SELECT: 1. ENabling
(main menu) 2. DISabling
3. INFO polling
4. other functions
FUNCTIONS: 1. function
(4) 2. system TEST
3. printout
4. configuration
CONFIGURATION: 1. user functions
(4.4) 2. user text
3. service functions
4. erase functions
ERASE data: 1. ERASE alarm counter
(4.4.4) 2. ERASE event memory
3. ERASE conf + sys data
4. ERASE element status
SERVICE 1. addr. line −> CONNECT
level : 2. addr. line −> DISCON.
(4.4.3) 3. test AI−LED’s ON/OFF
4. reconfigure addr. lines
5. horn/ctrl/RT −> OFF
6. TEST−alarm −> HORN
7. Visualizer ON/OFF
8. re−parametrise LON
Level SERVICE FUNCTIONS
> enter password?
hm: back to menu Stop: end operating
Details see page 101 (also via configuration tool SWE330A)
Details see page 71 (also via configuration tool SWE330A)
Details see page 115
Erase configuration data
ERASE data: 1. ERASE alarm counter
(4.4.4) 2. ERASE event memory
3. ERASE conf + sys data
4. ERASE element status
set USER DATA to DEFAULT? 1. no
> select? 2. yes
hm: back to menu Stop: end operating
SYSTEM temporarily BLOCKED
> writing data in flash−EPROM
wait.. system START
POWER OFF > RESET line(s) (50 sec.)
ready for CONFIGURATION (1st startup)
system on DEFAULT OPERATION
MON 2.6.03 12:10
consequence of option 2 see on page 53
The option ’4.4.4.3’ sets all system parameters to their
country specific default value.
This means that the physical structure (device types, line
types etc.) and the logical structure (detector zone types,
allocated trigger to conTrol zones, all links) will be
changed and all user texts will be deleted.
Proceed as indicated to the right.
1. Go to menu 4.4.4
2. Activate option 4.4.4.3
3. Wait until the flash-write cycle is over
4. Press key ’RESET’ (S1) on the main board K3X...
Autom. Restart of control panel with option 2