5.7 Define general functions
to define basic functions and alarm organization
to define the collective lines (only if K3M010 or K3M020 is equipped)
to overwrite the 4 basic passwords
to define the addressable lines / logical detector zones and conTrol zones
for data transfer FC330A PC (see page 70)
to define the floor repeater and control panels
to define the application on the serial ports
to define programmable inputs on K3X0x0 / K6
CONFIGURATION: 1. system data
(4.4.1) 2. collective line
3. password
4. addressable line
5. SWE330A
6. LON devices
7. serial ports
8. K6 inputs
Functions as displayed Purpose Selectable options/Remarks
last update: ##.##.## ##:##:##
password: USER TEXT ####, SERVICE ####
− date/time of last user function update and de-
fault passwords
number of COLLECTIVE lines ##
> change to?
− automatically initiated according to hardware
configuration
0 = without K3M...
4 = K3M010 used
12 = K3M020 used
number of HORN−lines: ##
> change to?
− automatically initiated according to hardware
configuration
2 = only master board used
4 = add-on pcb. K3M010 used
6 = add-on pcb. K3G050 used
number of alarm−contacts ##
> change to?
− automatically initiated according to hardware
configuration
0 = only master board K3X010
2 = only master board K3X020
4 = add-on pcb. K3M010 used
OFFSET coll. line no: > start no. 1 − ##
> selected ##, change?
− only relevant if K3M010 is used and only to be
changed if the collective lines do not have to
start with number 5
default = start with number 5
OFFSET horn no: > start no. 1 − ##
> selected ##, change?
− only to be changed if the control lines ‘horn’
do not have to start with number 1
default = start with number 1
OFFSET alarm contact no: > start 1 − ##
> selected ##, change?
− only to be changed if the controls (alarm con-
tacts) do not have to start with no. 1
default = start with number 1
MODE user text: 1. line 1=std / 2=user
> #, change? 2. line 1+2=user
− to define the extent of user text in alarm 1. text line 1 = standard text
text line 2 = user text
2. text line 1 = user text
text line 2 = user text
each element > NEW ZONE alarm 1. yes
selected #, change? 2. no
− to define that each device on alarm within the
same zone initiates a new zone alarm
SOUND MODE horn: 1. continuous
> #, ch.? 2. pulsating 3. set pulse
− to define sound mode on ’external alarm’
− common for all ‘horn’ control lines
1. continious signal
2. pulsating signal
3. set ’pulse length’
horn PULSE LENGTH / phase ACTIVE:
(3..20sec) > sel. ##/10 sec change?
− to define puls length of phase ACTIVE − value 3 = 0.3sec / 20 = 2sec
− one step = 0.1sec
− default = 5 (0.5sec)
horn PULSE LENGTH / phase INACTIVE:
(3..20sec) > sel. ##/10 sec change?
− to define puls length of phase INACTIVE − value 3 = 0.3sec / 20 = 2sec
− one step = 0.1sec
− default = 5 (0.5sec)
key ACKN. on alarm: 1. single action
> #, change? 2. double action
− to define function of key ’acknowledge’ at con-
trol panel
1. Actuation =
silence buzzer and horn
start CAC time ’V2’
2. 1st actuation =
silence buzzer and start ’V2’
2nd actuation
silence horn
behavior on immediate alarm AFTER reset:
S #:? 1.NEW AL 2.OFF 3.FLT 4.NEW BRK
− to define special function on immediate alarm
after reset
1. normal (realarm possible)
2. zone is disabled
3. zone is autom. set to fault