23 – 20
For frame size II only:
Fit support for the lower contacts together with the sensor covers
(1) Frame size II, 3200 A
(2) Frame size II, 800 - 2000 A
5 Establish plug connections
WARNING
Loss of overcurrent protection.
Incomplete connections of the sensor to the sensor wire harness may result in loss of overcurrent protection.
Make sure that the connectors are fully inserted and latched when connecting the sensor cable harness to the sensor.
89 lb-in
5 mm
10 Nm
(1)
(2)
Size
All lower screws
45 lb-in
5 mm
5 Nm
Size
All upper screws