Inputs/Outputs 9810 series - User manual
135 7EN05-0390-08
3. Click Expansion Modules > Option I/O Modules and select the module tab that
corresponds to the option module with the analog output you want to configure.
4. Select the analog output channel and click Edit. Enter the meter password if prompted. The
setup screen for that analog output is displayed.
5. Configure the analog output by selecting the parameter and clicking Edit.
Parameter Value/Range Description
Zero scale 0 to ±10
9
The minimum source value that matches the minimum
analog output signal.
Full scale 0 to ±10
9
The maximum source value that matches the maximum
analog output signal.
Port - The physical analog output port connection.
Mode
Voltage,
current
Determines whether the analog output is monitoring
voltage or current.
Digital inputs
Digital input applications
Digital inputs are typically used for monitoring the status of switches or contacts, such as status
contacts on circuit breakers.
They can also be used for pulse counting or input metering applications, such as WAGES (water,
air, gas, electricity, steam) monitoring, or conditional energy applications, or IRIG-B time
synchronization.
Pulse mode
If you set Input Mode to PULSE, a pulse is generated at the Trigger output when the State output
changes from OFF-to-ON. No pulse is generated when State changes from ON-to-OFF.
KYZ mode
If you set Input Mode to KYZ, a pulse is generated at the Trigger output for each change of state
transition, for example from OFF-to-ON and from ON-to-OFF transitions.