Display 9810 series - User manual
167 7EN05-0390-08
Auto-scaling feature
Measurement units on the meter display and webpages automatically scale, depending on the
value of PT Primary and CT Primary.
Voltage units are scaled based on the PT Primary value:
PT Primary value Units or scaling
< 1000 V
1000–999,999 kV
Current units are scaled based on the CT Primary value:
CT Primary value Units or scaling
< 1000 A
1000–999,999 kA
Power units are scaled according to the value of (CT Primary x PT Primary x 3):
(CT Primary x PT Primary x 3) value Units or scaling
< 1,000,000 kW, kVAR or kVA
1,000,000–999,999,999 MW, MVAR or MVA
≥ 1,000,000,000 GW, GVAR or GVA
Display screens
Display modes
Your meter has three display modes and provides access to your meter’s setup screens:
•
Normal Mode Screens (NORM) – In Norm mode, your meter automatically scrolls through a
series of customizable display screens. You can add or remove Norm mode display screens.
If there are no Norm mode display screens, the meter displays a message stating that there
are no available screens. To exit Norm mode, press the home button to access the display
modes selection screen.
•
Alt Display Mode (ALT) – In Alt mode, you can navigate to view the different alternate
screens. You cannot modify the default Alt mode display screens, but you can add custom
screens. To exit Alt display mode, select Normal Display Mode to access the display modes
selection screen.
•
Test Mode (TEST) – In Test mode, you can manually scroll through a series of default
screens. To exit Test mode, press the home button and select Exit Test Mode.
NOTE: In Test mode, your meter’s billing quantities stop accumulating and the data is sent
to special test mode registers. These registers are cleared when you exit Test mode.
Access your meter’s setup screens by pressing the home button in NORM, ALT or TEST mode.
To exit the setup screens, press the home button.