Name Priority Description Default
Over I unbal Medium Over unbalanced current alarm Disabled
Over V unbal Medium Over unbalanced voltage alarm Disabled
Over THD V1 - 3 Medium
Over total harmonic distortion
(THD) voltage alarms
Enabled
Over kW (P) sd Medium Over kW sliding demand alarm Disabled
Over I a - c, (1 - 3) 4 Medium Over current alarms Disabled
V1 - V3 Setpoint Medium Voltage setpoint alarms Disabled
Freq Setpoint Medium Frequency setpoint alarm Enabled
4-30 Volt Intrp Ph1 - 3 Low
4-30 voltage interruption power
quality alarms
Enabled
Transient/Waveshape High Transient alarm Disabled
Digital In Info Only
Digital input alarms
Number of alarms determined by
the total number of available digital
inputs
Note: Info Only alarms are not
displayed.
Enabled
Alarm information
You can view information about an alarm from your meter’s display.
Only alarms with a priority of low, medium, or high are displayed.
Parameter Description
Alarm The name of the alarm (for example, Over THD V1).
Priority Low, medium, or high alarm priority.
Date The date and time the alarm was triggered.
Duration The duration of the alarm (only applies to inactive alarms).
Ack
The date and time when the alarm was acknowledged (only applies to
acknowledged alarms).
Value
Active alarm: The minimum or maximum value detected when the alarm was
triggered.
Historic alarm: The minimum or maximum value detected during the duration
of the alarm.
Viewing and acknowledging alarms using the display
To view and acknowledge alarms using the display:
9810 series - User manual Alarms and alerts
7EN05-0390-08 182