5. Press the up or down icons to navigate alarms. A gray bar appears behind the active
selection.
6. To select the item(s) press Select for Enable/Disable.
7. Press Select to accept the change.
8. Press Select to confirm.
9. Complete the system maintenance tasks.
10. Enable the alarms you disabled.
Configuring setpoint/standard alarms using ION Setup
To configure standard alarm settings using ION Setup:
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Click Alarming > Standard.
4. Select a setpoint and click Edit.
5. Enter the password and click OK, if required.
The Setpoint Setup screen is displayed.
6. Configure the setpoint values as required.
7. Click Save to save the settings to your meter.
Parameter Value/Range Description
By Percentage
By Percentage/By
Value
When available, specifies if the Pickup and
Dropoff entries are by percentage or by value. If
the option is not available, pickup and dropoff
entries are by value.
Disabled/Enabled Checked/Unchecked
Forcing the alarm off disables all functions of the
associated input.
To stop an alarm from being displayed without
affecting other meter features, set the alarm
priority to Info Only.
Label String value
When available, lets you modify the default label
so it more clearly identifies the alarm. Letters,
numbers, and underscores are permitted.
Pickup Numeric value
Use this setting to provide a value for when the
alarm turns on.
Pickup Delay Numeric value
This specifies the number of seconds the input
must be over the alarm pickup value before the
alarm turns on.