Alarms and alerts 9810 series - User manual
193 7EN05-0390-08
To implement sag/swell limit learning using ION Setup:
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Click Alarming > Sag/Swell.
4. Select Voltage and click Learn.
NOTE: You can manually configure the limit values by selecting the parameter and clicking
Edit.
The Global Setpoint Learning screen is displayed.
5. Click Setup.
The Alarm Learning Setup screen is displayed.
Parameter Value/Range Description
Install mode
Automatic,
Manual
Automatic: the learned values are automatically
applied.
Manual: the learned values are stored for you to
review and enter.
Duration 1–365 Days for maximum learning duration.
Sag/swell limit learning parameters
6. Configure the sag/swell limit learning parameters and click Save.
7. Click Start to begin sag/swell limit learning.
Learning status and time remaining are indicated in the Learning Status box.
Click Abort to stop sag/swell limit learning.
8. Apply the learned sag/swell limits.
Automatic: the limits are automatically applied unless there are issues with the learning
process.
Manual: navigate to Alarming > Sag/Swell. Select Voltage and click Learn. Click
Install to apply the learned limits.
NOTE: If you click Install while learning is in progress (in either manual or automatic
installation mode), it stops the learning process and prompts you for confirmation that you
want to stop learning and install the learned limits. Once you have confirmed, the learned
limits are automatically installed or prepared for manual installation.
Implementing transient learning using ION Setup
You can use ION Setup to implement voltage transient learning, which analyzes your power
system and recommends settings.
NOTE: Your meter’s power system must be stable to learn valid transient thresholds.