197 7EN05-0390-08
Parameter Description Notes
Pre-trigger recording
Specifies, in seconds, how many
pre-event records to capture.
The actual number of records
set in the high-speed Sag/Swell
data recorder’s Pre-trigger
Records setup register = (2 x
system frequency) x (number of
seconds).
If system frequency is changed,
the recording duration for Pre-
trigger recording and Post-
trigger recording automatically
adjusts to reflect the new
frequency setting.
Post-trigger
recording
Specifies, in seconds, how many
post-event records to capture.
The actual number of records
set in the high-speed Sag/Swell
data recorder’s Post-trigger
Records = (2 x system
frequency) x (number of
seconds).
If system frequency is changed,
the recording duration for Pre-
trigger recording and Post-
trigger recording automatically
adjusts to reflect the new
frequency setting.
Total # of recordings
Specifies how many burst data
log sets to save in long-term
memory (NVRAM). The actual
number of records is configured
in the high-speed Sag/Swell
data recorder’s Depth setup
register = (Total # of recordings)
x (Pre-trigger Records + Post-
trigger Records + 1). For details
on how a data log set is
calculated, see "Data recorder
burst data" on page 213.
When burst data logging is
enabled, the equivalent number
of records for 2 burst data log
sets is allocated in short-term
memory (RAM). The actual
number of records set in the
high-speed Sag/Swell data
recorder’s Buffer Depth setup
register = 2 x (Pre-trigger
Records + Post-trigger Records
+ 1).
10. Click Next.
11. Use the Waveform Log Setup screen to configure the waveform recorder for Standard or
Delayed waveform capture.
NOTE: The Sag/Swell Logging Wizard does not support Extended waveform capture.
For more information on Standard, Delayed, and Extended waveform capture, see
"Waveform capture" on page 214.
Parameter Description
Waveform Depth
Specifies the maximum number of waveform records stored on the
meter.
Waveform Format
Specifies the number of samples per cycle and the number of
cycles that are stored in a waveform record.

Table of Contents