Hist Low Log (Data Rec 4)
Vll ab low V unbal low I avg low kVA tot low
Vll bc low Ia low I 4 low PF lag low
Vll ca low Ib low kW tot low PF lead low
Vll avg low Ic low kVAR tot low Freq low
Loss Log
The Loss Log (Data Rec 9) is configured to record loss values.
Factory settings for this data recorder:
Log depth = 3360 records (35 days)
Interval = 900 seconds (15 minutes)
By default, it logs the following values:
Parameter Description
MU Ia^2h int Phase A interval current squared hours
MU Ib^2h int Phase B interval current squared hours
MU Ic^2h int Phase C interval current squared hours
MU Vllab^2h int Phase A interval voltage Line-to-Line squared hours
MU Vllbc^2h int Phase B interval voltage Line-to-Line squared hours
MU Vllca^2h int Phase C interval voltage Line-to-Line squared hours
MU Vln a^2h int Phase A interval voltage Line-to-Neutral squared hours
MU Vln b^2h int Phase B interval voltage Line-to-Neutral squared hours
MU Vln c^2h int Phase C interval voltage Line-to-Neutral squared hours
Harmonics logs
Two harmonics logs record various harmonics data, including K-factor and Total Harmonic
Distortion (THD). These recorders are labeled Harm Mean Log and Harm High Log.
Factory settings for these data recorders:
Log depth = 840 records (35 days)
Interval = 3600 seconds (1 hour)
By default, they log the following values:
Harm Mean Log (Data Rec 7)
V1 THD mean I1 THD mean I1 K Fac mean
V2 THD mean I2 THD mean I2 K Fac mean
V3 THD mean I3 THD mean I3 K Fac mean
9810 series - User manual Logging
7EN05-0390-08 220