Logging 9810 series - User manual
221 7EN05-0390-08
Harm High Log (Data Rec 8)
V1 THD high I1 THD high I1 K Fac high
V2 THD high I2 THD high I2 K Fac high
V3 THD high I3 THD high I3 K Fac high
Energy and Demand Log
The EgyDmd Log (Data Rec 10) records energy and demand data used by energy management
software to generate reports.
Factory settings for this data recorder:
Log depth = 3360 records (35 days)
Interval = 900 seconds (15 minutes)
By default, it logs the following values:
Parameter Description
kWh del Active energy delivered
kWh rec Active energy received
kWh del-rec Active energy delivered minus received
kVARh del Reactive energy delivered
kVARh rec Reactive energy received
kVARh del-rec Reactive energy delivered minus received
kVAh del+rec Apparent energy delivered plus received
kW sd del-rec Active power demand delivered minus received
kVAR sd del-rec Reactive power demand delivered minus received
kVA sd del+rec Apparent power demand delivered plus received
Daily Nominal Log
The DailyNom Log (Data Rec 39) provides information about the meter’s nominal settings.
Factory settings for this data recorder:
Log depth = 450 records
Interval = Triggered on demand
By default, it logs the following values from the Factory module’s setup registers:
Parameter Description
FAC1 Vnominal Nominal voltage setting
FAC1 NomFreqNum Expected frequency of operation