Resets
Resets overview
Resets allow you to clear accumulated parameters stored on your meter, reinitialize the meter or
reinitialize meter accessories.
Meter resets clear your meter’s onboard data logs and other related information. Resets are
typically performed after you make changes to the meter’s basic setup parameters to clear invalid
or obsolete data to prepare the meter for active service.
NOTE: Revenue-locked meters must be unlocked to perform resets that impact revenue data.
For more information, see "Revenue locking your meter" on page 279.
Option modules reset
Perform an option module reset if your option modules are not communicating with your meter.
During an option module reset, the option module may not operate normally, and digital and
analog outputs may change state.
WARNING
UNINTENDED OPERATION
Failure to follow these instructions can result in death, serious injury, or equipment
damage.
Do not use this device for critical control or protection of persons, animals, property, or
equipment.
You can reset your meter’s option module bus using ION Setup or the display. This power cycles
all the modules attached to your meter. If you have queued firmware updates for option modules
on your meter’s internal SFTP site, the firmware updates are performed.
By default, your meter is configured to automatically perform an option module bus reset to help
keep the option modules operating normally. Contact Technical Support for instructions on
changing this default configuration.
Available resets
You can perform meter resets using ION Setup, the meter webpages or the display.