9810 specifications 9810 series - User manual
293 7EN05-0390-08
AC control power
Operating range
50/60 Hz ± 10%: 90–480 V ± 10%
400 Hz: 90–120 V ± 10%
Burden (meter only)
Maximum: 16.5 W/38 VA @ 480 V (45–65 Hz)
Maximum: 13 W/24 VA @ 120 V (400 Hz)
Burden (fully optioned meter)
Maximum: 40 W/80 VA @ 480 V (45–65 Hz)
Maximum: 36 W/58 VA @ 120 V (400 Hz)
Ride-through time (no optional
accessories)
100 ms (6 cycles at 60 Hz) typical, 120 V AC
400 ms (24 cycles at 60 Hz) typical, 240 V AC
1200 ms (72 cycles at 60 Hz) typical, 480 V AC
DC control power
Operating range 110–480 V DC ± 10%
Burden (meter only) Maximum: 13.5 W at 480 V DC
Burden (fully optioned meter) 37 W at 480 V DC
Overvoltage category III
Control power
DC control power
Operating range 20–60 V DC ± 10%
Burden (meter only) Maximum: 15 W at 20–60 V DC
Burden (fully optioned meter) Maximum: 38 W at 20–60 V DC
Overvoltage category III
Low-voltage DC control power
Number 4
Type Form A solid-state
Reference voltage 40 V
Maximum load voltage 30 V AC/60 V DC
Maximum load current 75 mA
ON resistance 13–40 Ω at 25 °C (77 °F)
Signal type Continuous or pulse
Pulse frequency 25 Hz
Digital output (Form A)
Number 2
Type Form C mechanical relay
Relay output (Form C)

Table of Contents