Installation and commissioning 9810 series - User manual
66 7EN05-0390-08
Option modules are monitored and controlled by the meter’s ION modules. External I/O modules
are mapped to the corresponding ION modules:
Option module physical position ION module mapping
Module A to Module D Port A to Port D
Option module terminal connector label ION module mapping
Analog inputs A1 to A(n) Analog Input module A1 to A(n)
Analog outputs Q1 to Q(n) Analog Output module Q1 to Q(n)
Digital inputs S1 to S(n) Digital Input module S1 to S(n)
Digital/relay outputs R1 to R(n) Digital Output module R1 to R(n)
Maximum number of option modules
Up to four option modules are supported per device.
Limitations:
•
Only one Fiber Ethernet module may be installed.
•
Depending on the type and quantity of option modules attached to your meter, you may need
to reduce your meter’s maximum operating temperature or limit the number of option
modules. See "Environmental characteristics" on page 295 for more information.