Communications 9810 series - User manual
87 7EN05-0390-08
When configuring communications parameters, ensure you maintain at least one communication
path that allows full access to your device; otherwise, you may permanently lose the ability to
change your device’s configuration and access to additional data.
NOTICE
LOSSOFACCESS
Failure to follow these instructions can result in loss of access to the device.
Ensure you maintain sufficient access to communicate with and configure your device.
NOTE: You cannot change the Ethernet port number assignments through the display.
To manage network protocol control using the display:
1. Press the Home button on the display.
2. Navigate to Setup Menu > Ethernet Port Enable Setup.
3. Press Edit. Enter your meter’s password, if prompted.
4. Press the up or down icons to navigate available Ethernet protocols. A gray bar appears
behind the active selection.
5. Press Enable/Disable.
6. Press Select to accept the change.
7. Press Select to confirm.
Serial communications
The meter supports serial communications through its onboard RS-485 ports.
RS-485
In an RS-485 network, there is one client device, typically an Ethernet to RS-485 gateway. It
provides the means for RS-485 communications with multiple server devices, such as meters. For
applications that require only one dedicated computer to communicate with the server devices, a
USB to RS-485 converter can be used to connect to the server device.
Up to 32 devices can be connected on a single RS-485 bus.
RS-485 wiring
Connect the devices on the RS-485 bus in a point-to-point configuration, with the (+) and (-)
terminals from one device connected to the corresponding (+) and (-) terminals on the next
device.