Switch SW1 on the MAPNET Transceiver Daughter Card is a bank of eight dip switches. From
left to right (see figure below) these switches are designated as SW1-1 through SW1-8. The
function of these switches is as follows:
•
SW 1-1
. This switch sets the baud rate for the serial communication line running between
the daughter card and the 4100 CPU. Set this switch to ON.
•
SW1-2 through SW1-8
. These switches set the card’s address within the 4100 FACP.
(These switches must be set to the value assigned to the card by the 4100 Programmer.) Refer
to Table 1 for a complete list of the switch settings for all of the possible card addresses.
Move a switch to the down position to turn it ON or to the up position to turn it OFF.
18765432
Figure 1. DIP Switch SW1
Continued on next page
Setting the Card Address Switch
Switches
OFF
ON
Dip Switches 1-2 through 1-8
set the Card Address. Figure
shows an Address of 3. Refer
to Table 1 for switch settings.
Baud Rate
Switch (SW 1-1)
Must Be Set to
ON