EasyManua.ls Logo

SINAMICS G120 - Page 65

SINAMICS G120
116 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SINAMICS G120
Standard inverters 0.37 kW to 250 kW (0.5 hp to 400 hp)
PM260 Power Modules –
11 kW to 55 kW (15 hp to 75 hp)
4/65
Siemens D 11.1 · 2009
4
Selection and ordering data
To ensure that a suitable Power Module is selected, the following
currents should be used for applications:
rated output current for applications with light overload
(LO)
base load current for applications with high overload (HO)
With reference to the rated output current, the modules support
at least 2-pole to 6-pole low-voltage motors, e.g. the new 1LE1
motor series (please refer to the Appendix for further informa-
tion). The rated power is merely a guide value. For a description
of the overload performance, please refer to the general techni-
cal specifications of the Power Modules.
Rated power
1)
Rated output
current
2)
I
rated
Power
based on the
base load current
3)
Base load
current
3)
I
H
Frame
size
SINAMICS G120
PM260 Power Module
without integrated line filter
SINAMICS G120
PM260 Power Module
with integrated class A
line filter
kW hp A kW hp A Order No. Order No.
500 690 V 3 AC
11.0 15 14 7.5 10 10 FSD 6SL3225-0BH27-5UA1 6SL3225-0BH27-5AA1
15.0 20 19 11 15 14 FSD 6SL3225-0BH31-1UA1 6SL3225-0BH31-1AA1
18.5 25 23 15 20 19 FSD 6SL3225-0BH31-5UA1 6SL3225-0BH31-5AA1
30 40 35 22 30 26 FSF 6SL3225-0BH32-2UA1 6SL3225-0BH32-2AA1
37 50 42 30 40 35 FSF 6SL3225-0BH33-0UA1 6SL3225-0BH33-0AA1
55 75 62 37 50 42 FSF 6SL3225-0BH33-7UA1 6SL3225-0BH33-7AA1
new new
new new
new new
new new
new new
new new
1)
Rated power based on the rated output current I
rated
. The rated output
current I
rated
is based on the duty cycle for light overload (LO).
2)
The rated output current I
rated
is based on the duty cycle for light overload
(LO). These current values are valid for 690 V and are stamped on the
rating plate of the Power Module.
3)
The base load current I
H
is based on the duty cycle for high overload (HO).
© Siemens AG 2009