SINAMICS G120
Standard inverters 0.37 kW to 250 kW (0.5 hp to 400 hp)
PM260 Power Modules –
11 kW to 55 kW (15 hp to 75 hp)
4/65
Siemens D 11.1 · 2009
4
■
Selection and ordering data
To ensure that a suitable Power Module is selected, the following
currents should be used for applications:
• rated output current for applications with light overload
(LO)
• base load current for applications with high overload (HO)
With reference to the rated output current, the modules support
at least 2-pole to 6-pole low-voltage motors, e.g. the new 1LE1
motor series (please refer to the Appendix for further informa-
tion). The rated power is merely a guide value. For a description
of the overload performance, please refer to the general techni-
cal specifications of the Power Modules.
Rated power
1)
Rated output
current
2)
I
rated
Power
based on the
base load current
3)
Base load
current
3)
I
H
Frame
size
SINAMICS G120
PM260 Power Module
without integrated line filter
SINAMICS G120
PM260 Power Module
with integrated class A
line filter
kW hp A kW hp A Order No. Order No.
500 … 690 V 3 AC
11.0 15 14 7.5 10 10 FSD 6SL3225-0BH27-5UA1 6SL3225-0BH27-5AA1
15.0 20 19 11 15 14 FSD 6SL3225-0BH31-1UA1 6SL3225-0BH31-1AA1
18.5 25 23 15 20 19 FSD 6SL3225-0BH31-5UA1 6SL3225-0BH31-5AA1
30 40 35 22 30 26 FSF 6SL3225-0BH32-2UA1 6SL3225-0BH32-2AA1
37 50 42 30 40 35 FSF 6SL3225-0BH33-0UA1 6SL3225-0BH33-0AA1
55 75 62 37 50 42 FSF 6SL3225-0BH33-7UA1 6SL3225-0BH33-7AA1
new new
new new
new new
new new
new new
new new
1)
Rated power based on the rated output current I
rated
. The rated output
current I
rated
is based on the duty cycle for light overload (LO).
2)
The rated output current I
rated
is based on the duty cycle for light overload
(LO). These current values are valid for 690 V and are stamped on the
rating plate of the Power Module.
3)
The base load current I
H
is based on the duty cycle for high overload (HO).