Electrical Connection SMA Solar Technology AG
28 SMC9-11TLRP-IEN100640 Installation Guide
5.2.3 Additional Grounding of the Housing
If a second protective conductor connection is required in the country of installation, you can also
ground the inverter using a second protective conductor on the connection terminal on the enclosure.
Procedure
1. Insert the stripped grounding cable (D) under the
clamping clip (C) (max. cross-section 16 mm²).
2. Screw the clamping clip tight with screw (A) and
tooth lock washer (B).
The toothing of the tooth lock washer must face
toward the clamping clip.
The inverter's enclosure is additionally grounded.
You can ground multiple inverters as shown in the diagram below: