SMA Solar Technology AG Electrical Connection
Installation Guide SMC9-11TLRP-IEN100640 51
5.9.2 Frequency-dependent Active Power Limitation P(f)
Activating this function enables active power limitation P depending on the grid frequency f
AC
. The
process used complies with the Medium Voltage Regulation valid in Germany. However, the settings
can also be adjusted to the requirements of other countries or utility operators by means of software
parameters.
The "P-WCtlHzMod" parameter allows you to select the frequency-dependent active power limitation
P(f). 2 settings can be selected.
This process is deactivated on delivery.
Procedures and Configuration Parameters
Configuration Options for "On"
Default settings
In the table below, default settings are marked with *.
Procedure Setting Description
P-WCtlHzMod Off* The process is deactivated.
On The active power is throttled in accordance with the
characteristic curve.
Setting Parameters Description Value range Default
On P-HzStr Start frequency (nominal
frequency + setting) for active
power limitation.
0 ... 5 Hz 0.20 Hz
P-WGra Steepness of the active power
limitation (gradient).
10 ... 100 %/Hz 40 %/Hz
P-HzStop Frequency (nominal frequency +
setting) for resetting the active
power limitation.
0 ... 5 Hz 0.05 Hz