Troubleshooting SMA Solar Technology AG
72 SMC9-11TLRP-IEN100640 Installation Guide
Shutdown Temporary inverter fault.
Corrective measures
Contact the SMA Serviceline.
STM Timeout Internal program run fault.
Corrective measures
If this fault occurs often, contact the SMA Serviceline.
Vac-Bfr
Vac-Srr
The grid voltage on line 2 is no longer within the permissible range
("Bfr" or "Srr" is an internal message that has no meaning for the user).
This code can be caused by any of the following conditions:
Grid disconnected (line circuit breaker, fuse),
•AC cable is broken or
AC cable is highly resistive.
For safety reasons, the inverter disconnects itself from the grid.
Corrective measures
Check the grid current and grid connection on the inverter.
If the grid voltage lies outside the acceptable range because of
local grid conditions, ask the utility operator if the voltages can be
adjusted at the feed-in point or if they agree to changes in the
values of the monitored operational limits (operating parameters:
Vac-Min and Vac-Max).
If the grid frequency is within the tolerable range, yet "Vac-Bfr," or
"Vac-Srr" faults are still being displayed, please contact the SMA
Serviceline.