6 Connection
SMA Solar Technology AG
Installation Manual MDSEN-US-40-IA-en-13 15
6 Connection
6.1 Cable Requirements
UV resistance of connection cables
Connection cables to be laid outdoors must be UV-resistant or routed in a UV-resistant cable
channel.
Cable type Requirements
Cable for shielding the
analog input and the
temperature inputs
Number of conductors: 1
Conductor cross-section: 1.5mm² (16AWG)
Cable length: 120mm (4.71in)
Connection cables for
temperature inputs
Number of insulated conductors for tolerance ±2°C (±3.6°F): at
least two
Number of insulated conductors for tolerance ±0.5°C (±0.9°F): at
least four
Shielding: yes
Conductor cross-section with four-conductor connection technology:
at least 4x0.25mm² (24AWG)
Maximum cable length for four-conductor connection technology:
20m (65ft)
Conductor cross-section for two-conductor connection technology: at
least 2x0.25mm² (24AWG)
Maximum cable length for two-conductor connection technology:
2.5m (8ft)
External cable diameter: 4.5mm to 7.0mm (0.18in to 0.28in)
Connection cable for
analog input
Number of conductors: at least 2
Shielding: yes
Conductor cross-section: 0.2mm² to 1.5mm² (32AWG to
16AWG)
Maximum cable length: 30m (98ft)
Connection cable for
S0 interface
Number of conductors: 2
Shielding: yes
Conductor cross-section: 0.2mm² to 1.5mm² (32AWG to
16AWG)
Maximum cable length: 30m (98ft)
6.2 Preparing the Connection Cable
Prepare each connection cable for connection and the cable for shielding the analog input and the
temperature inputs in accordance with the following procedure for connection to the multipole
terminal blocks.