6 Connection
6.1 Cable Requirements
UV resistance of connection cables
Connection cables to be laid outdoors must be UV-resistant or routed in a UV-resistant cable
channel.
Cable type Requirements
Cable for shielding the
analog input and the
temperature inputs
☐ Number of conductors: 1
☐ Conductor cross-section: 1.5mm² (16AWG)
☐ Cable length: 120mm (4.71in)
Connection cables for
temperature inputs
☐ Number of insulated conductors for tolerance ±2°C (±3.6°F): at
least two
☐ Number of insulated conductors for tolerance ±0.5°C (±0.9°F): at
least four
☐ Shielding: yes
☐ Conductor cross-section with four-conductor connection technology:
at least 4x0.25mm² (24AWG)
☐ Maximum cable length for four-conductor connection technology:
20m (65ft)
☐ Conductor cross-section for two-conductor connection technology: at
least 2x0.25mm² (24AWG)
☐ Maximum cable length for two-conductor connection technology:
2.5m (8ft)
☐ External cable diameter: 4.5mm to 7.0mm (0.18in to 0.28in)
Connection cable for
analog input
☐ Number of conductors: at least 2
☐ Shielding: yes
☐ Conductor cross-section: 0.2mm² to 1.5mm² (32AWG to
16AWG)
☐ Maximum cable length: 30m (98ft)
Connection cable for
S0 interface
☐ Number of conductors: 2
☐ Shielding: yes
☐ Conductor cross-section: 0.2mm² to 1.5mm² (32AWG to
16AWG)
☐ Maximum cable length: 30m (98ft)
6.2 Preparing the Connection Cable
Prepare each connection cable for connection and the cable for shielding the analog input and the
temperature inputs in accordance with the following procedure for connection to the multipole
terminal blocks.