7 Configuration
SMA Solar Technology AG
Installation Manual MDSEN-US-40-IA-en-13 27
4. In the context menu, select [Starting the installation assistant].
5. Select [Save and next] until you reach the Irradiation temperature step.
6. Under Module temperature and External temperature, select the required setting value
for the temperature display in the event of an error.
7.3 Configuring the Irradiation Sensor
You must set the irradiation sensor to current or voltage operation depending on the connection
type (current or voltage) and configure the characteristic curve of the irradiation sensor.
You can set the current or voltage operation and configure the characteristic curve via the device
parameters or using the installation assistant.
Signal value 1
of characteristic
curve of the
analog input
Signal value 2
of characteristic
curve of the
analog input
Signal value [mA, V]
Y value 1
of characteristic curve
of the analog input
Y value 2
of characteristic curve
of the analog input
2
Irradiation [W/m ]
Figure 13: Characteristic curves of an irradiation sensor (example)
Settings via device parameters
In the following table, you will find all parameters that are needed to set the characteristic curve.
Object name Parameter Display group Settings
InOut.AnIn.Func Function of the ana-
log input
Device > Inputs/outputs >
Analog input > Function
Irradiation sensor 0 to
20mA (InsolSns20mA)
Irradiation sensor 0 to
10V (InsolSns10V)
InOut.AnIn.Sig-
Val1NoUnt
Signal value 1 of
characteristic curve
of the analog input
Device > Inputs/outputs >
Analog input > Signal value
1
0.00 to 20.00V or mA
InOut.AnIn.Sig-
Val2NoUnt
Signal value 2 of
characteristic curve
of the analog input
Device > Inputs/outputs >
Analog input > Signal value
2
0.00 to 20.00V or mA