Error Cause and corrective measure
The fans do not start up. The required temperature has not been reached.
Corrective measures:
To check the function of the fans, turn down the thermostat.
The fans start up.
The circuit breaker has tripped.
Corrective measures:
Check whether apparent damage is visible in the corresponding electrical circuit.
If any damage is present, remove it.
Switch the circuit breaker back on.
The fans are defective.
Corrective measures:
Replace the fans. Contact the Service (see Section17, page256).
The voltage supply of the MVPowerStation failed.
Corrective measures:
Ensure that the supply voltage is present (see error "Supply voltage is not
present").
The cabling is damaged.
Corrective measures:
Ensure that the cabling is intact.
The HV/HRC fuse has
tripped.
The HV/HRC fuse is outdated.
Corrective measures:
Replace all out-of-date fuses (see documentation of the medium-voltage
switchgear).
An error occurred on the MV transformer.
Corrective measures:
Ensure that no errors are present on the MV transformer (see documentation of the
MV transformer).
The cabling is damaged.
Corrective measures:
Ensure that the cabling is intact.
9 Troubleshooting
SMA Solar Technology AG
System Manual 117MVPS22JP-SH-en-11