Error Cause and corrective measure
The MV transformer cannot
be reconnected.
The MV transformer is defective.
Corrective measures:
Replace the MV transformer. Contact the Service (see Section17, page256).
There is air in the MV transformer.
Corrective measures:
Check the protective devices.
Ensure that no air is in the MV transformer.
Refill the oil.
The MV transformer is too warm.
Corrective measures:
Read off the temperature of the MV transformer from the contact thermometer.
Allow the MV transformer to cool down.
If the error reoccurs, contact the Service (see Section17, page256).
The relay in the station subdistribution is not working properly.
Corrective measures:
Ensure that the relay in the station subdistribution is correctly functioning.
Ensure that the cabling of the relay is intact.
9.3 Troubleshooting in the Inverter
9.3.1 Activating Alert in the Event of a Fault
You can be notified by e-mail of events that have occurred. This allows a rapid response to failures in the PV power
plant and minimizes downtimes. The alert is deactivated upon delivery.
Communication unit reports an error-type event after two averaging intervals
The communication unit reports error-type events which have persisted twice as long as the time set for averaging.
Example: If the averaging setting is 15 minutes, the communication unit will report an error once it has existed for
longer than 30 minutes.
Procedure:
1. Log into the user interface (see Section12.8.1, page177).
2. Select SunnyCentral > Settings > Data transmission.
3. In the field Notification active, select yes.
4. Select an option in the field Multiple Notices (24h/48h):
Option Explanation
yes You will receive an e-mail immediately upon occurrence of an event. If the event
persists after 24 hours and 48 hours, the e-mail will be sent again.
no You will receive an e-mail once when an event occurs. An e-mail with error-type
events is sent after two averaging intervals.
5. In the field E-mail address, enter the e-mail address. If an e-mail is to be sent to multiple e-mail addresses,
separate the e-mail addresses with commas.
9 Troubleshooting
SMA Solar Technology AG
System ManualMVPS22JP-SH-en-11118