Danger to life due to electric shock or electric arc if live components are touched
If the MVPowerStation and its devices are not correctly disconnected, dangerous voltages may be present in the
components which, if touched, will result in death or serious injury.
• Disconnect the MVPowerStation (see Section7.6, page101).
• After switching off the inverter, wait at least 15minutes before opening it to allow the capacitors to discharge
completely.
• Ensure that the MVPowerStation and its devices are voltage-free.
Procedure:
1. Switch the inverter to Stop (see Section7.4.1, page100).
2. Connect the supply voltage (see Section7.9.1, page103).
3. Measure the voltage at the supply voltage output between L1 and N.
☑ The voltage is approximately 230V.
✖ Voltage deviates significantly?
• Contact Service partner.
4. Measure the voltage at the supply voltage output of the UPS at -X400 terminal5 and -X402 terminal5.
☑ The voltage is approximately 24V.
✖ Voltage deviates significantly?
• Contact Service partner.
5. Disconnect the supply voltage (see Section7.4.4, page100).
6. Measure the time until the communication unit switches off.
☑ The communication unit switches off after 15seconds at the earliest.
✖ The communication unit switches off earlier?
• Contact Service partner.
10.5.11 Checking the AC Disconnection Unit
The inverter is optionally equipped with an AC disconnection unit. If a circuit breaker manufactured by ABB is installed,
it needs to be checked. If a circuit breaker by LS Industrial Systems is installed, no checking is necessary.