12.4 Cable Entry
12.4.1 Inserting the Cables through the Base Plates
12.4.1.1 Overview of the Base Plates on the MVPowerStation
The MVPowerStation is fitted with base plates through which the cables are inserted. The cables should be protected
between the foundation and the MVPower Station. Cable protection measures are customer responsibility.
Figure 52: Position of the base plates and openings for cables
Position Designation
A Base plate of the SunnyCentral in the MVPowerStation 1000SC-JP / 1250SC-JP /
1600SC-JP
B Base plate of the SunnyCentral in the MVPowerStation 500SC-JP / 630SC-JP / 800SC-JP
C Base plate of the medium-voltage switchgear:
6 openings for single-core cables; maximum cable diameter: 55mm
D Base plate with cable glands for the data cables and grounding cables:
3 x PG9 for cable diameters from 6mm to 8mm
3 x PG11 for cable diameters from 8mm to 10.5mm
4 x PG16 for cable diameters from 13mm to 16mm
4 x PG21 for cable diameters from 17mm to 20mm
12.4.1.2 Inserting Cables through the Base Plates of the Inverters
Requirement:
The service platform in front of the inverter compartment must be installed.
Procedure:
1. Open the inverter compartment (see Section12.1, page159).
2. Cut the cables to the required length. Allow for some reserve.
12 Periodic Actions
SMA Solar Technology AG
System Manual 167MVPS22JP-SH-en-11