Name Description Value/range Explanation Default
value
Surge Arrester1
*
Alarm contact (e.g. theft protec-
tion for Sunny String-Monitor)
Activ High Contact activated when volt-
age is present
0
Activ Low Contact activated when no
voltage is present
Deactivated Contact deactivated
Surge Arrester2
*
Alarm contact Activ High Contact activated when volt-
age is present
0
Activ Low Contact activated when no
voltage is present
Deactivated Contact deactivated
* To change these parameters, you must enter the installer password.
** These parameters are only visible after entering the installer password.
14.2.4 Zone Monitoring
Name Description Value/range Explanation Default
value
DcCfg.AmpMax[1] Maximum current of
input 1
0Ato 500A ‒ 0A
DcCfg.AmpMax[2] Maximum current of
input 2
0Ato 500A ‒ 0A
DcCfg.AmpMax[3] Maximum current of
input 3
0A to 500A ‒ 0A
DcCfg.AmpMax[4] Maximum current of
input 4
0A to 500A ‒ 0A
DcCfg.AmpMax[5] Maximum current of
input 5
0A to 500A ‒ 0A
DcCfg.AmpMax[6] Maximum current of
input 6
0A to 500A ‒ 0A
DcCfg.AmpMax[7] Maximum current of
input 7
0A to 500A ‒ 0A
DcCfg.AmpMax[8] Maximum current of
input 8
0A to 500A ‒ 0A
MaxTol Tolerance in percent
by which the input
current may deviate
from the mean value
0.1%…100% ‒ 4.0%