Name Description Value/range Explanation Default
value
DevFunc Device function --- Default, no action ---
ResetMeasuring Restarts the algorithm. All measured
value are deleted.
Factory Resets all parameters to default set-
tings
Ackn Acknowledge errors --- Default, no action ---
Quit Acknowledgment of the present er-
ror
AlarmEna Activation of the error
analysis
--- Default, no action ---
Off No error analysis. Only measured
value are sent.
On Error analysis activated. Error mes-
sages are generated, if deviations
occur (see Section14.1.4.2, page
220).
14 Operating Data and Parameters
SMA Solar Technology AG
System ManualMVPS22JP-SH-en-11240