EasyManua.ls Logo

SMA MEDIUM VOLTAGE POWER STATION 500SC-JP - Page 248

SMA MEDIUM VOLTAGE POWER STATION 500SC-JP
258 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
AC Output
Transformer vector groups Dy11y11 / YNd11d11
Displacement power factor cosφ 0.9overexcitedto0.9underexcited
* information based on inverter
Efficiency
Maximum efficiency 97.6 %
European weighted efficiency 97.4 %
General Data
Width x height x depth 6058mmx2591mmx2438mm
Weight < 14 t
Operating temperature range −25°C to +40°C / −25°C to +55°C*
Self-consumption in operation** < 3800W
Standby consumption*** < 200W + 1200W
Internal auxiliary supply voltage 230V / 400V (3/N/PE), 50Hz / 60Hz
Maximum permissible value for relative humidity (non-
condensing)
15%to95%
Maximum operating altitude above mean sea level 1000 m
Maximum operating altitude above MSL for option "In-
stallation at high altitudes"
1001m to 2000m / 2001m to 3000m
Fresh air consumption** 6000m
3
/h
Degree of protection of medium-voltage compartment as
per IEC60529
IP23D
Degree of protection of transformer compartment and in-
verter compartment as per IEC60529
IP00
* optional
** information based on inverter
*** separated according to consumption of the inverter and standby power losses of the transformer
15 Technical Data
SMA Solar Technology AG
System ManualMVPS22JP-SH-en-11248

Table of Contents