5.7.2.2 Connecting Optical Fibers via Optical Fiber Pigtail
Figure 35: Position of the splice box
Position Designation
A Splice box
Optical fiber requirements:
The optical fiber cables must be equipped with a 50μm multi-mode optical fiber.
The optical fibers must be fitted with a subscriber connector.
Damage to optical fibers due to too tight bend radii
Excessive bending or kinking will damage the optical fibers.
Observe the minimum permissible bend radii of the optical fibers.
Procedure:
1. Disassemble the panels (see Section12.3.1.2, page164).
2. Insert the optical fibers in the inverter (see Section12.4.3, page171).
3. Remove the splice box from the top-hat rail:
4. Open the enclosure of the splice box.
5 Installation
SMA Solar Technology AG
System Manual 67MVPS22JP-SH-en-11