Procedure:
1. Log into the user interface (see Section12.8.1, page177).
2. Select the tab Parameters.
3. Set the parameter DevFunc to AutoDetect_SSMU.
4. Select the button [Save].
5. Select the tab Instantaneous values.
6. Select SSMUNoOf and check the number of detected Sunny String-Monitors.
Once all Sunny String-Monitors have been detected, detect them via the communication unit(see
Section6.5.11.5, page89).
If only some of the SunnyString‑Monitors have been detected, use SunnyCentralString‑MonitorController to
redetect them (see Section6.5.11.4, page89).
6.5.11.4 Redetecting the SunnyString-Monitors via the SunnyCentralString-
MonitorController
1. Log into the user interface (see Section12.8.1, page177).
2. Select the tab Parameters.
3. Set the parameter DevFunc to Retry.
4. Select the button [Save].
5. Select the tab Instantaneous values.
6. Select SSMUNoOf and check the number of detected Sunny String-Monitors.
Once all Sunny String-Monitors have been detected, detect them via the communication unit(see
Section6.5.11.5, page89).
If only some of the SunnyString-Monitors have been detected, contact the Service .
6.5.11.5 Detecting the Sunny String-Monitors via the Communication Unit
1. Log into the user interface (see Section12.8.1, page177).
2. Select Data > Detection.
3. In the field Total number of devices to be detected, enter the number of Sunny String-Monitors +2.
4. Select the button [Start detection].
☑ The communication unit starts detecting all inverters and displays its progress. Once all devices have been
detected, the message ### Device detection finished ### is displayed.
☑ The Sunny String-Monitors have been detected.
6.5.11.6 Adjusting the Identification of the Sunny String-Monitors
1. Log into the user interface (see Section12.8.1, page177).
2. Select the first Sunny String-Monitor from the device list.
3. Select the tab Parameters.
4. Select the parameter SSMId and allocate a unique identification number to the SunnyString-Monitor. Note the
identification number.
5. Adjust the identification of the remaining Sunny String-Monitors using the same process.
6 Commissioning
SMA Solar Technology AG
System Manual 89MVPS22JP-SH-en-11