7.2.2 Connection Points for Supply Voltage
Figure 39: Connection points for supply voltage
Position Designation
1 Transformer for internal power supply
2 Station subdistribution
3 Lighting
4 Outlet
5 Inverter
6 Communit
A Transformer circuit breaker
B Circuit breaker of the entire station subdistribution
C Circuit breakers of the station subdistribution devices
7.3 Disconnecting the Supply Voltages of the Station Subdistribution
The circuit breakers for the different devices of the MVPowerStation are located in the station subdistribution.
Procedure:
1. For disconnecting the inverters from the supply voltage, switch off the circuit breakers VoltageSupplySC1 and
VoltageSupplySC2.
2. For disconnecting the Communit and its lighting from the supply voltage, switch off the circuit breaker
VoltageSupplyLighting/Communit.
3. For disconnecting the optional fans from the supply voltage, switch off the circuit breaker Fan.
4. For disconnecting the outlet from the supply voltage, switch off the circuit breaker Socket.
5. For disconnecting the entire MVPowerStation from the supply voltage, switch off the main switch
VoltageSupplyPowerOutlet.
6. For disconnecting the transformer for internal power supply, switch off the transformer protective device.
7 Disconnecting and Reconnecting