8 Configuration
SMA Solar Technology AG
Operating manual STP15-25TL-30-BE-en-17 49
The basic procedure for changing operating parameters is explained in another section (see
Section8.3 "Changing Operating Parameters", page46).
Procedure:
• Select the parameter Cycle time of the OptiTrac Global Peak algorithm or
MPPShdw.CycTms and set the required time interval. The ideal time interval is usually six
minutes. This value should only be increased if the shading situation changes extremely slowly.
☑ The inverter optimizes the MPP of the PV system at the predetermined time interval.
• In order to deactivate the SMAOptiTracGlobalPeak feature, select the parameter OptiTrac
Global Peak switched on or set MPPShdw.IsOn to Off.