Grid configurations TN-C, TN-S, TN-CS, TT(if V
N_PE
<30V), IT, Delta
IT, split phase
National standards and approvals, as per
01/2017*
AS4777, C10/11/2012, CEI0-21,
EN50438:2013, DINEN62109-1, G83/2,
IEC62109-2, NBR16149, NEN-EN50438,
NRS097-2-1, RD1699/413, VDE 0126-1-1,
VDE-AR-N4105, VFR2014
* IEC62109-2: In order to meet the requirements of this standard, there must be a link to SunnyPortal
with the fault alert via e-mail activated.
Climatic Conditions
Installation in accordance with IEC60721-3-4, Class4K4H
Extended temperature range -40°C to +60°C
Extended humidity range 0% to 100%
Extended air pressure range 79.5kPato106kPa
Transport in accordance withIEC60721-3-4, Class2K3
Extended temperature range -25°C to +70°C
Equipment
DC connection SUNCLIX DC connector
AC connection Spring-cage terminal
Speedwire interface As standard
Webconnect interface As standard
WLAN As standard
DC Load-Break Switch
Electrical endurance in the event of short circuit,
at nominal current of 10A
At least 50switching operations
Maximum switching current 35A
Maximum switching voltage 800V
Maximum PV power 11kW
Torques
Screws wall mounting Hand-tight
Screws connection cap 3.5Nm
SUNCLIX swivel nut 2.0Nm
AC swivel nut Hand-tight
15Technical Data
SMA Solar Technology AG
Operating ManualSB15-25-1VL-40-BE-en-1188