6.4 Connecting the PV Array (DC)
6.4.1 Conditions for the DC Connection
Requirements for the PV modules of the connected strings:
Same type
–Same number
Identical alignment
Identical tilt
The connection cable of the PV modules must be equipped with connectors. The DC connectors
for the DC connection are included in the delivery.
The following limiting values at the DC input of the inverter must not be exceeded:
Use of Y adapters for parallel connection of strings
Y adapters may not be visible within close proximity of the inverter or freely accessible.
The DC electric circuit must not be interrupted by adaptors.
Observe the procedure for disconnecting the inverter as described in section
8"Disconnecting the Inverter from Voltage Sources" (page58).
Sunny Boy Maximum input voltage Maximum input current
SB 2000HF‑30 700 V 12 A
SB 2500HF‑30 700 V 15 A
SB 3000HF‑30 700 V 15 A