EasyManua.ls Logo

SMA SUNNY BOY 2000HF - Abortion of the Self-Test

SMA SUNNY BOY 2000HF
96 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Commissioning SMA Solar Technology AG
56 SB20HF-30HF-IA-IEN120431 Installation Manual
Minimum frequency
After the maximum frequency test, the minimum frequency
test takes place and the inverter shows the adjacent
display message for 5 seconds.
During the test sequence, the frequency limit applied is
shown in the display of the inverter. The frequency limit is
increased successively until the shut‑down threshold is
reached and the inverter disconnects from the power
distribution grid.
Once the inverter has disconnected from the power distribution grid, the display successively shows
each of the following values one after the other for 10 seconds:
•Disconnection value,
•Calibration value,
•Reaction time.
The change between the first and second display takes places every 2.5 seconds.
7.3.3 Abortion of the Self‑Test
If, during the self‑test, an unexpected disconnection requirement occurs, the self‑test is aborted.
The same applies if the DC voltage is so low that the feed‑in cannot be continued.
The inverter then shows the adjacent display
message for 10 seconds.
Restart the self‑test as described in the following
section 7.3.4"Restarting the Self‑Test" (page57).

Table of Contents

Other manuals for SMA SUNNY BOY 2000HF

Related product manuals