SMA Solar Technology AG Messages
Installation Guide SB20_25_30HF-IEN102911 71
35 < Insulation resist. >
< Check generator >
The inverter has detected a ground fault in
the PV generator. However, the inverter
continues feeding into the grid.
Check the strings for ground faults, as
described in section 11.1”Checking
the PV Generator for a Ground
Fault” (page74).
The installer of the PV generator must
remedy the ground faults before you
re-connect the affected string.
< Ground fuse fault >
< Check ground fuse >
The inverter has detected a ground voltage
in the grounding path.
Check the ground fuse as described
in the in installation guide of the
SMAplug-in Grounding. Check the
strings for ground faults, as described
in section 11.1”Checking the PV
Generator for a Ground Fault”
(page74).
38 < DC overcurrent >
< Check generator >
An overcurrent condition occurs on the
DCside of the inverter and the inverter
switches off.
If this event occurs often:
Check the layout and the wiring of
the PV generator.
39 < Wait for DC start conditions >
< Start cond. not met >
The input power or the voltage of the
PVmodules is not sufficient for feeding into
the grid.
Wait for higher irradiation.
If this event recurs at medium
irradiation, check the PV system
design and correct the connection of
the PV generator.
42 < Wrong earthing type; check earthing
set>
The polarity of the grounding set does not
correspond to the polarity set at the
inverter.
Check polarity of grounding set.
Remove grounding set.
Turn grounding set 180° and
reconnect with correct polarity.
60 - 64 < Self diagnosis >
< Interference device >
Contact the SMAServiceline (see
section 15”Contact” (page93)).
65 < Self diagnosis >
< Overtemperature >
The inverter switches off due to too high
temperature
Ensure sufficient ventilation.
Check heat dissipation, as described
in section 9.1”Checking Heat
Dissipation” (page63).
66 < Self diagnosis >
< Overload >
Contact the SMAServiceline (see
section 15”Contact” (page93)).
Event no. Display message and cause Corrective measures