13 Technical Data
SMA Solar Technology AG
Operating manual SBxx-1AV-41-BE-en-12 101
AC Output
SB3.0-1AV-41 SB3.6-1AV-41 SB4.0-1AV-41
Rated power at 230V,
50Hz
3000W 3680W 4000W
Maximum apparent
AC power at cosφ=1
3000VA 3680VA 4000VA
Rated grid voltage 230V 230V 230V
Nominal AC voltage 220V/230V/240
V
220V/230V/240
V
220V/230V/240
V
AC voltage range* 180V to 280V 180V to 280V 180V to 280V
Nominal AC current at
220V
13.7A 16A 18.2A
Nominal AC current at
230V
13.1A 16A 17.4A
Nominal AC current at
240V
12.5A 15.4A 16.7A
Maximum output cur-
rent
13.7A 16A 18.2A
Total harmonic distor-
tion of the output cur-
rent with total harmonic
distortion of the AC
voltage <2%, and AC
power >50% of the
rated power
≤3% ≤3% ≤3%
Maximum output cur-
rent under fault condi-
tions
29A 29A 29A
Inrush current <20% of the nominal
AC current for a
maximum of 10ms
<20% of the nominal
AC current for a
maximum of 10ms
<20% of the nominal
AC current for a
maximum of 10ms
Rated power frequency 50Hz 50Hz 50Hz
AC power frequency* 50Hz/60Hz 50Hz/60Hz 50Hz/60Hz
Operating range at AC
power frequency
50Hz
45Hz to 55Hz 45Hz to 55Hz 45Hz to 55Hz
Operating range at AC
power frequency
60Hz
55Hz to 65Hz 55Hz to 65Hz 55Hz to 65Hz