13 Technical Data
SMA Solar Technology AG
Operating manual SBxx-1AV-41-BE-en-12 103
SB5.0-1AV-41 SB6.0-1AV-41
Maximum short-circuit current,
input B*
20 A 20 A
Maximum reverse current into
the PV array
0A 0A
Number of independent MPP
inputs
2 2
Strings per MPP input 2 2
Surge category in accordance
with IEC60664-1
II II
* In accordance with IEC62109-2: ISC PV
AC Output
SB5.0-1AV-41 SB6.0-1AV-41
Rated power at 230V, 50Hz* 5000W 6000W
Maximum apparent AC power at cosφ=1** 5000VA 6000VA
Rated grid voltage 230V 230V
Nominal AC voltage 220V/230V/240
V
220V/230V/240
V
AC voltage range*** 180V to 280V 180V to 280V
Nominal AC current at 220V 22.8A 26.1A
Nominal AC current at 230V 22A 26.1A
Nominal AC current at 240V 21A 25A
Maximum output current**** 22.8A 26.1A
Total harmonic distortion of the output current
with total harmonic distortion of the AC voltage
<2%, and AC power >50% of the rated power
≤3% ≤3%
Maximum output current under fault conditions 29A 29A
Inrush current <20% of the nominal
AC current for a
maximum of 10ms
<20% of the nominal
AC current for a
maximum of 10ms
Rated power frequency 50Hz 50Hz
AC power frequency*** 50Hz/60Hz 50Hz/60Hz
Operating range at AC power frequency 50Hz 45Hz to 55Hz 45Hz to 55Hz
Operating range at AC power frequency 60Hz 55Hz to 65Hz 55Hz to 65Hz
Power factor at rated power 1 1