6 Maintenance
SMA Solar Technology AG
Maintenance ManualSCCPXT-E7-WA-en-3746
Procedure:
1. Switch the inverter to Stop.
2. Connect the supply voltage (see Section4.3.1, page28).
☑ The fans start to run for a few moments.
✖ The fans do not start up?
• Please contact (see Section9, page68).
6.4.1.2 Checking the Heating Elements and Hygrostat
Figure 11: Position of the heating element and the hygrostat
Position Designation
A Hygrostat
B Heating element
DANGER
Danger to life due to electric shock or electric arc if live components are touched
• Switch off the inverter and wait at least 15minutes before opening it to allow the capacitors to discharge
completely.
• Disconnect the inverter (see Section4, page26).
CAUTION
Risk of burns due to hot components
Some components of the product can get very hot during operation. Touching these components can cause burns.
• Observe the warnings on all components.
• During operation, do not touch any components marked with such warnings.
• After switching off the product, wait until any hot components have cooled down sufficiently.
• Wear suitable personal protective equipment for all work on the product.
Procedure:
1. Switch the inverter to Stop.
2. Connect the supply voltage (see Section4.3.1, page28).
3. Set the hygrostat to the minimum value. To do this, pull the selector switch out slightly.
Tip: the hygrostat is adjusted correctly if the relay of the hygrostat emits an audible click.